| Type |
2 Vertical Direct Fired Propane Vaporizers AE-120, combined with
Venturi Gas / Air Mixer HVS-20MM
print window |
| Capacity |
Vaporizer:
2 x 120 Gallons Per Hour Propane Vaporization at 0 °F.
Mixer: 20 MMBTU/h LP/Air Mixture @ 5 - 8 (15) psi.
High Pressure Systems over 10 psig require compressed air. |
| Design Temperature |
650 °F. |
| Design Pressure |
250 PSIG |
| Test Pressure |
375 PSIG |
| Manufactured Construction |
Vaporizing Tube Conforms to ASME Boiler & Pressure Vessel Code, Section I.
Conforms to latest edition of NFPA #58. |
| Approvals |
Factory Mutual (FM) or Industrial Risk Insurers
(IRI).
Canadian Standards Association (CSA) and CRN Number.
ASME 'U' Stamp. |
| Standard Safety Features |
- Dual Liquid Level Control
- Pressure Relief Valve Protection (Vapor Tube)
- Pilot Thermocouple
- High Mixed Gas Pressure
- Low Mixed Gas Pressure
- Low Propane Vapor Pressure
- Pressure Relief Valve Protection (Surge Tank)
- Manual Drain
|
|
System Controls |
- United Electric Pressure Switches
|
| Burner Input |
2 x 140,000 BTU/hr |
| Liquid Inlet Connection |
3/4" NPT |
| Mixed Gas Outlet Connection |
2" NPT |
| Electrical Requirement |
120 VAC, Single Phase, 60 Hz, 2 Amp. |
| Dimensions |
106" x 48" x 80" (L x W x H) |
|
Available Options |
- Electronic System Controls with Allen-Bradley
PLC and Rosemount Pressure Transmitters
- Modem, Ethernet, or Wireless Interface
for remote monitoring and control
- Color LCD Display with Touch Screen
Operator Interface
- Naturally aspirated Venturi System for
up to 12(15) psi delivery pressure
- High-Pressure mixing system for up to 50
psi delivery pressure
|
| Catalog Drawing |
click