| Type |
HVS-20 MM Venturi Gas / Air Mixer
print window |
| Capacity |
20 MMBTU/h LP/Air Mixture @ 5 - 8
(15) psi
5.04 MMkcal/h LP/Air Mixture @ 0.35 - 0.6 (1) bar
High Pressure Systems over 15 psi / 1 bar require compressed air. |
|
Number of Venturi Trains |
2 |
| Surge Tank Capacity |
120 gal
0.45 m³ |
| Surge Tank Design Pressure |
50 psi
3.5 bar |
| Manufactured Construction |
Conforms to ASME Boiler & Pressure Vessel Code.
Conforms to latest edition of NFPA #58. |
| Approvals |
Factory Mutual (FM) or Industrial Risk Insurers
(IRI);
Canadian Standards Association (CSA). |
| Standard Safety Features |
- High Mixed Gas Pressure
- Low Mixed Gas Pressure
- Low Propane Vapor Pressure
- Pressure Relief Valve Protection (Surge Tank)
|
| Vapor Supply Connection |
3/4" NPT |
| Mixed Gas Outlet Connection |
2" NPT |
| Electrical Requirement |
AC 115 V, Single Phase, 5 A
AC 220/240 V, Single Phase, 5 A |
| Dimensions
(approximate) |
54" x 54" x 83" (L x W x H)
1.37 m x 1.37 m x 2.11 m |
| Dry Weight
(approximate) |
850 lbs.
386 kg |
|
Available Options |
- Electronic Controls with Allen-Bradley
PLC
- Modem, Ethernet, or Wireless Interface
for remote monitoring and control
- Color LCD Display with Touch Screen
Operator Interface
- Naturally aspirated Venturi System for
up to 12(15) psi delivery pressure
- High-Pressure mixing system for up to 50
psi delivery pressure
- Ex-proof configuration of System
Controls
- Low-Profile Compact Configuration (for
easy air shipment)
|
| Catalog Drawing |
click here to see
catalog drawing |